
The Stratosphere
The Stratosphere
is engineered to deliver exceptional performance while seamlessly integrating into modern building designs. Perfect for projects with curtain wall systems, these units are designed to complement and match the aesthetic of the surrounding architecture.
-
• Custom extruded aluminum enclosure with PPG Duranar finish
Designed to mate to and match new curtain wall, coordinated with curtain wall trade partner
• High performance fan with 24V EC motor and factory configured CFM set point (limited field air balancing required)
• Pressure independent control valve with factory configured GPM set-point (limited field water balancing required)
• Pre-configured direct digital controls
• Single point connection for power, control, and communication
• Quick connect low voltage wiring
• Fully insulated piping package
• Unit specific laser engraved tagging
• Tested for performance, sound, and leakage of entire assembly
• Designed for easy access for units, controls, and piping
• Throwaway filter
-
• Units individually boxed, packaging materials used for field protection
• Units delivered on pallets as coordinated with installing contractor to fit in hoist
• Staging and storage will be coordinated with installing contractor
• Submittals to include unique unit layout drawings for each floor with: – Tagging
Risers locations
Electrical connections
-
• 3rd party certified unit performance test on each unit type (by Intertek)
• 3rd party certified unit sound test on each unit type (by Intertek)
• Testing report submitted for record and available online via laser etched QR code
• Factory pressure test for each unit utilizing NIST traceable instrumentation
Pressure recorded electronically at 1 second intervals
-
• TecspecSystem Optimized ValveTM for variable air and water controls
• Factory installed return air sensor
no wall thermostat and associated field wiring required)
• Factory installed condensate/leak sensor and associated controls for valve shutoff
• Factory installed entering water temperature sensor
• No field wiring required except for quick connect inter unit power and communication
• Stand alone controls
• Each unit has over 100 BACnet points available for future BMS integration
-
Electrical Requirements
Provide 120V, 20 Amp. Circuit per Submittal Drawing
Each 20 Amp Circuit with serve (24) Units utilizing (3) Drops
Mechanical Requirements
Receive and Install Unit
Connect low voltage interconnecting cable between Sections
Final Piping Connections
Future BMS Integration Requirements
(2) BACnet IP Drops per floor for future BMS Integration (typical)
Each Unit will be factory configured with a unique device instance (BACnet Address) to allow seamless BMS Integration (No Dip Switch Settings or Field Addressing Required)
Each unit will be factory configured with system alarm points for future BMS Integration (No Field Alarm Programming Required)
Each Unit will be factory configured with Energy Management routines for future BMS Integration (No field Programming required)
Let’s Work Together.
Interested in working together? Fill out some info and we will be in touch shortly! We can't wait to hear from you!